CVE-2024-47901

published 23 Oct 2024 · updated 23 Oct 2024

A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All…

10.0CriticalCVSS 10.0EPSS 1%

No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 1%. Fixed in InterMesh 7177 Hybrid 2.0 Subscriber V8.2.12 and InterMesh 7707 Fire Subscriber V7.2.12.

A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All versions < V7.2.12 only if the IP interface is enabled (which is not the default configuration)). The web server of affected devices does not sanitize the input parameters in specific GET requests that allow for code execution on operating system level. In combination with other vulnerabilities (CVE-2024-47902, CVE-2024-47903, CVE-2024-47904) this could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.

Affected

Vendors, products and packages with version ranges

VendorProductVersionsFixed
SiemensInterMesh 7177 Hybrid 2.0 Subscriber<V8.2.12V8.2.12
SiemensInterMesh 7707 Fire Subscriber<V7.2.12V7.2.12