CVE-2024-47903

published 23 Oct 2024 · updated 23 Oct 2024

A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All…

5.8MediumCVSS 5.8EPSS 0%

No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 0%. Fixed in InterMesh 7177 Hybrid 2.0 Subscriber V8.2.12 and InterMesh 7707 Fire Subscriber V7.2.12.

A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All versions < V7.2.12 only if the IP interface is enabled (which is not the default configuration)). The web server of affected devices allows to write arbitrary files to the web server's DocumentRoot directory.

Affected

Vendors, products and packages with version ranges

VendorProductVersionsFixed
SiemensInterMesh 7177 Hybrid 2.0 Subscriber<V8.2.12V8.2.12
SiemensInterMesh 7707 Fire Subscriber<V7.2.12V7.2.12

Timeline

Every event on this vulnerability

Related

Other vulnerabilities in Siemens, strongest first

10.0CriticalCISA KEVPublic exploit
10.0CriticalCISA KEVPublic exploit

Embed

A live severity badge for an advisory, README or ticket

CVE-2024-47903 severity on Zeptric[![CVE-2024-47903](https://zeptric.io/badge/cve/CVE-2024-47903.svg)](https://zeptric.io/cve/CVE-2024-47903)