PublishedCVE-2025-26390·
9.8Critical
No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 1%. Fixed in OZW672 V6.0 and OZW772 V6.0.
A vulnerability has been identified in OZW672 (All versions < V6.0), OZW772 (All versions < V6.0). The web service of affected devices is vulnerable to SQL injection when checking authentication data. This could allow an unauthenticated remote attacker to bypass the check and authenticate as Administrator user.
Vendors, products and packages with version ranges
| Vendor | Product | Versions | Fixed |
|---|---|---|---|
| Siemens | OZW672 | <V6.0 | V6.0 |
| Siemens | OZW772 | <V6.0 | V6.0 |
Every event on this vulnerability
Other vulnerabilities in Siemens, strongest first
A live severity badge for an advisory, README or ticket