A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF…
No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 0%. Fixed in SIMATIC ET *, SIMATIC ET V1.3, SIMATIC ET V6.0.1 and 7 more.
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
Affected
Vendors, products and packages with version ranges
| Vendor | Product | Versions | Fixed |
|---|---|---|---|
| Siemens | SIMATIC ET | =V4.2.0, <V1.3, <V6.0.1, >=V4.2.0 <V4.2.5, <V4.2.2 | *, V1.3, V6.0.1, V4.2.5, V4.2.2 |
| Siemens | SIMATIC PN/MF Coupler | * | |
| Siemens | SIMATIC PN/PN Coupler | <V6.0.0 | V6.0.0 |
| Siemens | SIPLUS ET 200MP IM 155-5 PN HF | =V4.2.0 | * |
| Siemens | SIPLUS ET 200SP IM 155-6 PN HF | >=V4.2.0 <V4.2.5 | V4.2.5 |
| Siemens | SIPLUS NET PN/PN Coupler | <V6.0.0 | V6.0.0 |
Timeline
Every event on this vulnerability
Related
Other vulnerabilities in Siemens, strongest first
Embed
A live severity badge for an advisory, README or ticket