Alarm receiver stops delivering alarms after a malformed alarm notification
No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 0%. Fixed in 1.0.4.
P-Net before 1.0.4 sets the alarm receiver state to waiting for confirmation before the data of a received alarm notification is parsed. If the parsing fails the state is not restored, and later alarm notifications of the same priority are discarded without acknowledge until the Application Relationship is released. The Application Relationship and the cyclic data exchange keep working. The attacker must be able to send an alarm notification in the context of an established Application Relationship and requires ADJACENT network access.
Affected
Vendors, products and packages with version ranges
| Vendor | Product | Versions | Fixed |
|---|---|---|---|
| RT-Labs | <1.0.4 | 1.0.4 |
Timeline
Every event on this vulnerability
Embed
A live severity badge for an advisory, README or ticket