CVE-2026-17539

published 3 Sep 2026 · updated 3 Sep 2026

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference…

5.9MediumCVSS 5.9EPSS 0%

No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 0%. No fixed version is recorded.

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.

Affected

Vendors, products and packages with version ranges

VendorProductVersionsFixed
Hitachi Energy>=12.7.1 <=12.7.7, >=13.5.1 <=13.5.4, >=13.6.1 <=13.6.3, >=13.7.1 <=13.7.8, >=13.8.1 <=13.8.2

Timeline