upsmon: remote OS command injection (RCE) via attacker-controlled ups.alarm in NOTIFYCMD execution
No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 1%. No fixed version is recorded.
Network UPS Tools is a collection of programs which provide a common interface for monitoring and administering UPS, PDU and SCD hardware. From 2.8.3 to 2.8.5, upsmon in clients/upsmon.c inserts the server-supplied ups.alarm value into shell commands executed by notify(), async_notify(), and wall(). When a monitored device reports an ALARM state and an operator has configured NOTIFYCMD with EXEC in NOTIFYFLAG ALARM, shell metacharacters in the alarm text are evaluated on POSIX or Windows and can execute arbitrary operating-system commands as the upsmon account, which is commonly root. An attacker can control the value through a malicious or compromised upsd, a man-in-the-middle on a plaintext upsd to upsmon connection, or a compromised UPS device whose driver supplies the alarm upstream of upsd; TLS between upsd and upsmon does not mitigate the compromised-device path. This vulnerability is fixed in 2.8.6.
Affected
Vendors, products and packages with version ranges
| Vendor | Product | Versions | Fixed |
|---|---|---|---|
| networkupstools | >=2.8.3 <=2.8.5 |
Timeline
Every event on this vulnerability
Embed
A live severity badge for an advisory, README or ticket