A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862),…
No exploitation in the wild has been reported. EPSS puts the chance of exploitation in the next 30 days at 0%. Fixed in Desigo DXR2 V01.21.233.16-7862, Desigo PXC3 V01.21.233.16-7862, Desigo PXC4 V02.21.194.36-2715 and 3 more.
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.
Affected
Vendors, products and packages with version ranges
| Vendor | Product | Versions | Fixed |
|---|---|---|---|
| Siemens | Desigo DXR2 | <V01.21.233.16-7862 | V01.21.233.16-7862 |
| Siemens | Desigo PXC3 | <V01.21.233.16-7862 | V01.21.233.16-7862 |
| Siemens | Desigo PXC4 | <V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens | Desigo PXC5.E003 | <V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens | Desigo PXC5.E24 | <V02.21.194.36-2715 | V02.21.194.36-2715 |
| Siemens | Desigo PXC7 | <V02.21.194.36-2715 | V02.21.194.36-2715 |
Timeline
Every event on this vulnerability
Related
Other vulnerabilities in Siemens, strongest first
Embed
A live severity badge for an advisory, README or ticket